Product code: BC/BD-t-2X563AD1-B19 C

Heat rejection i
445.40 kW
Air flow
103,783 m³/h
Fans
10 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 103,783 m³/h
External surface 1,148.2 m²
Inner volume 173.4 dm³
Fin materialAluminium
Net weight 905 kg
Fans
Quantity 10
Diameter 630 mm
Speed 1,330 rpm
Power 12,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-t-2X563AD1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
445.395 kW Fluid flow 77.25 m³/h Pressure drop 50.4 kPa
Heat rejection · Low speed (Y)
349.187 kW Fluid flow 60.56 m³/h Pressure drop 32.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 268.32 not rated not rated not rated not rated not rated
40 445.40 268.70 not rated not rated not rated not rated
45 616.04 444.02 269.05 not rated not rated not rated
50 784.55 613.21 442.94 269.50 not rated not rated
55 952.05 780.36 610.92 442.28 270.10 not rated
60 1119.00 946.56 776.96 609.37 442.08 270.99

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 212.78 not rated not rated not rated not rated not rated
40 349.19 213.41 not rated not rated not rated not rated
45 480.24 348.65 214.03 not rated not rated not rated
50 609.54 478.82 348.39 214.56 not rated not rated
55 738.03 607.34 477.92 348.18 215.58 not rated
60 866.08 735.10 605.84 477.14 348.96 216.94

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 445.395 77.25 50.4
Low speed (Y) 349.187 60.56 32.7

Dimensions

Dimension drawing of BC/BD-t-2X563AD1-B19 C
Dimension drawing
Dimensions as drawn
A 4950 mm
B 1220 mm
C 2310 mm
F 1050 mm
G 450 mm
E 4600 mm
H 900 mm
I 2260 mm
K 5300 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 4950 mm
Width 2310 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.