Skip to Content

Dry cooler BC/BD-t-2x280JC5-B03 C

Dry cooler BC/BD-t-2x280JC5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2x280JC5-B03 C

Heat rejection i
163.43 kW
Air flow
37,305 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 37,305 m³/h
External surface 605.2 m²
Inner volume 86.7 dm³
Fin materialAluminium
Net weight 707 kg
Fans
Quantity 4
Diameter 800 mm
Speed 435 rpm
Power 1,300 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 38.0 dB(A)
Sound power 70.0 dB(A)
Energy class B
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-t-2x280JC5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
163.425 kW Fluid flow 28.35 m³/h Pressure drop 72.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
123.316 kW Fluid flow 21.39 m³/h Pressure drop 43.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 100.57 not rated not rated not rated not rated not rated
40 163.43 100.39 not rated not rated not rated not rated
45 224.34 162.66 100.24 not rated not rated not rated
50 284.64 223.06 162.03 100.17 not rated not rated
55 344.64 282.87 222.01 161.58 100.21 not rated
60 404.48 342.39 281.40 221.22 161.36 100.40

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 76.70 not rated not rated not rated not rated not rated
40 123.32 76.53 not rated not rated not rated not rated
45 168.41 122.67 76.39 not rated not rated not rated
50 213.03 167.37 122.14 76.31 not rated not rated
55 257.43 211.61 166.50 121.76 76.32 not rated
60 301.72 255.64 210.43 165.87 121.57 76.46

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 163.425 28.35 72.3
Low speed (Y) 123.316 21.39 43.8

Dimensions

Dimension drawing of BC/BD-t-2x280JC5-B03 C
Dimension drawing
Dimensions as drawn
A 3850 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 3600 mm
H 1750 mm
I 2260 mm
K 4150 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 4150 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.