Skip to Content

Dry cooler BC/BD-t-563AC1-B01 C

Dry cooler BC/BD-t-563AC1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-563AC1-B01 C

Heat rejection i
163.63 kW
Air flow
39,393 m³/h
Fans
5 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 39,393 m³/h
External surface 465.3 m²
Inner volume 57.4 dm³
Fin materialAluminium
Net weight 494 kg
Fans
Quantity 5
Diameter 630 mm
Speed 860 rpm
Power 3,000 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 50.0 dB(A)
Sound power 81.5 dB(A)
Energy class D
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-t-563AC1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · Single phase
163.625 kW Fluid flow 28.37 m³/h Pressure drop 43.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Single phase

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 97.92 not rated not rated not rated not rated not rated
40 163.63 98.14 not rated not rated not rated not rated
45 227.06 163.25 98.34 not rated not rated not rated
50 289.74 226.19 162.97 98.58 not rated not rated
55 352.06 288.40 225.50 162.83 98.88 not rated
60 414.19 350.28 287.33 225.05 162.89 99.29

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
Single phase 163.625 28.37 43.6

Dimensions

Dimension drawing of BC/BD-t-563AC1-B01 C
Dimension drawing
Dimensions as drawn
A 4850 mm
B 1220 mm
C 1230 mm
F 1050 mm
G 450 mm
E 4600 mm
H 900 mm
I 1180 mm
K 5100 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 4850 mm
Width 1230 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.