Skip to Content

Dry cooler BC/BD-t-2x280LB5-B03 C

Dry cooler BC/BD-t-2x280LB5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2x280LB5-B03 C

Heat rejection i
169.84 kW
Air flow
41,862 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 41,862 m³/h
External surface 622.5 m²
Inner volume 88.6 dm³
Fin materialAluminium
Net weight 787 kg
Fans
Quantity 4
Diameter 800 mm
Speed 435 rpm
Power 1,300 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 38.0 dB(A)
Sound power 70.0 dB(A)
Energy class B
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-t-2x280LB5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
169.836 kW Fluid flow 29.45 m³/h Pressure drop 77.9 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
134.179 kW Fluid flow 23.27 m³/h Pressure drop 51.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 103.08 not rated not rated not rated not rated not rated
40 169.84 102.87 not rated not rated not rated not rated
45 234.74 169.02 102.69 not rated not rated not rated
50 299.03 233.37 168.32 102.58 not rated not rated
55 363.04 297.12 232.19 167.77 102.55 not rated
60 426.89 360.60 295.47 231.25 167.44 102.65

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 82.12 not rated not rated not rated not rated not rated
40 134.18 81.96 not rated not rated not rated not rated
45 184.68 133.50 81.80 not rated not rated not rated
50 234.68 183.55 132.92 81.69 not rated not rated
55 284.44 233.11 182.58 132.46 81.66 not rated
60 334.08 282.46 231.77 181.81 132.18 81.74

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 169.836 29.45 77.9
Low speed (Y) 134.179 23.27 51.2

Dimensions

Dimension drawing of BC/BD-t-2x280LB5-B03 C
Dimension drawing
Dimensions as drawn
A 5150 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 4900 mm
H 2400 mm
I 2260 mm
K 5450 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 5450 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.