Dry cooler BC/BD-t-2x380GB5-B03 C

Dry cooler BC/BD-t-2x380GB5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2x380GB5-B03 C

Heat rejection i
169.73 kW
Air flow
48,595 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 48,595 m³/h
External surface 408.5 m²
Inner volume 64.4 dm³
Fin materialAluminium
Net weight 756 kg
Fans
Quantity 6
Diameter 800 mm
Speed 435 rpm
Power 1,900 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 40.0 dB(A)
Sound power 72.0 dB(A)
Energy class C
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-t-2x380GB5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
169.734 kW Fluid flow 29.46 m³/h Pressure drop 111.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
131.822 kW Fluid flow 22.86 m³/h Pressure drop 70.9 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 100.61 not rated not rated not rated not rated not rated
40 169.73 100.90 not rated not rated not rated not rated
45 237.17 169.70 101.19 not rated not rated not rated
50 304.03 236.82 169.72 101.50 not rated not rated
55 370.65 303.43 236.63 169.87 101.88 not rated
60 437.13 369.78 303.03 236.64 170.17 102.35

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 78.91 not rated not rated not rated not rated not rated
40 131.82 79.19 not rated not rated not rated not rated
45 183.34 131.89 79.47 not rated not rated not rated
50 234.38 183.22 132.02 79.80 not rated not rated
55 285.21 234.10 183.23 132.26 80.17 not rated
60 335.92 284.77 234.00 183.42 132.65 80.65

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 169.734 29.46 111.2
Low speed (Y) 131.822 22.86 70.9

Dimensions

Dimension drawing of BC/BD-t-2x380GB5-B03 C
Dimension drawing
Dimensions as drawn
A 3500 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 3250 mm
H 1050 mm
I 2260 mm
K 3800 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3800 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.