BC/BD-t-2X463AA5-B19 C
204.32 kW
Defrost: None
Product code: BC/BD-t-391OB1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 69,309 m³/h |
|---|---|
| External surface | 325.7 m² |
| Inner volume | 44.2 dm³ |
| Fin material | Aluminium |
| Net weight | 522 kg |
| Quantity | 3 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 8,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 96.4 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-t-391OB1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 116.73 | not rated | not rated | not rated | not rated | not rated |
| 40 | 204.04 | 117.42 | not rated | not rated | not rated | not rated |
| 45 | 289.42 | 204.28 | 118.04 | not rated | not rated | not rated |
| 50 | 374.17 | 289.27 | 204.55 | 118.63 | not rated | not rated |
| 55 | 458.61 | 373.65 | 289.22 | 204.88 | 119.24 | not rated |
| 60 | 542.89 | 457.74 | 373.30 | 289.34 | 205.35 | 119.89 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 204.039 | 35.41 | 96.8 |
| A | 4550 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 4300 mm |
| H | 1400 mm |
| I | 1180 mm |
| K | 4850 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4850 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.