BC/BD-t-2X563AA5-B01 C
203.63 kW
Defrost: None
Product code: BC/BD-2X363CC5-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 68,120 m³/h |
|---|---|
| External surface | 626.8 m² |
| Inner volume | 101.6 dm³ |
| Fin material | Aluminium |
| Net weight | 598 kg |
| Quantity | 6 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 7,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-2X363CC5-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 116.51 | not rated | not rated | not rated | not rated | not rated |
| 40 | 203.72 | 117.14 | not rated | not rated | not rated | not rated |
| 45 | 288.86 | 203.77 | 117.69 | not rated | not rated | not rated |
| 50 | 373.34 | 288.41 | 203.84 | 118.19 | not rated | not rated |
| 55 | 457.49 | 372.41 | 288.06 | 203.97 | 118.71 | not rated |
| 60 | 541.48 | 456.12 | 371.65 | 287.86 | 204.21 | 119.25 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 99.44 | not rated | not rated | not rated | not rated | not rated |
| 40 | 172.75 | 99.96 | not rated | not rated | not rated | not rated |
| 45 | 244.11 | 172.73 | 100.41 | not rated | not rated | not rated |
| 50 | 314.85 | 243.64 | 172.74 | 100.83 | not rated | not rated |
| 55 | 385.30 | 313.97 | 243.29 | 172.82 | 101.26 | not rated |
| 60 | 455.58 | 384.01 | 313.25 | 243.07 | 173.02 | 101.75 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 203.723 | 35.36 | 39.1 |
| Low speed (Y) | 172.745 | 29.98 | 29.1 |
| A | 3000 mm |
|---|---|
| B | 1200 mm |
| C | 2360 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2800 mm |
| H | 900 mm |
| I | 2310 mm |
| K | 3300 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 3300 mm |
|---|---|
| Width | 2360 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.