BC/BD-480CB5-B03 C
133.14 kW
Defrost: None
Product code: BC/BD-t-463AB5-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 46,180 m³/h |
|---|---|
| External surface | 236.5 m² |
| Inner volume | 39.8 dm³ |
| Fin material | Aluminium |
| Net weight | 371 kg |
| Quantity | 4 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 5,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 89.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-t-463AB5-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 75.25 | not rated | not rated | not rated | not rated | not rated |
| 40 | 132.87 | 75.75 | not rated | not rated | not rated | not rated |
| 45 | 189.11 | 132.98 | 76.19 | not rated | not rated | not rated |
| 50 | 244.91 | 188.88 | 133.08 | 76.58 | not rated | not rated |
| 55 | 300.52 | 244.38 | 188.71 | 133.21 | 76.96 | not rated |
| 60 | 356.00 | 299.67 | 243.93 | 188.61 | 133.41 | 77.35 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 64.41 | not rated | not rated | not rated | not rated | not rated |
| 40 | 113.03 | 64.83 | not rated | not rated | not rated | not rated |
| 45 | 160.37 | 113.09 | 65.19 | not rated | not rated | not rated |
| 50 | 207.27 | 160.12 | 113.15 | 65.53 | not rated | not rated |
| 55 | 254.00 | 206.75 | 159.93 | 113.25 | 65.85 | not rated |
| 60 | 300.60 | 253.20 | 206.32 | 159.82 | 113.40 | 66.20 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 132.869 | 23.06 | 39.4 |
| Low speed (Y) | 113.032 | 19.62 | 29.6 |
| A | 3950 mm |
|---|---|
| B | 1220 mm |
| C | 1230 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 3700 mm |
| H | 900 mm |
| I | 1180 mm |
| K | 4200 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 3950 mm |
|---|---|
| Width | 1230 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.