BC/BD-t-2x280LC5-B03 C
185.05 kW
Defrost: None
Product code: BC/BD-t-563AB1-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 56,882 m³/h |
|---|---|
| External surface | 349.0 m² |
| Inner volume | 46.4 dm³ |
| Fin material | Aluminium |
| Net weight | 460 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 6,300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-t-563AB1-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 107.16 | not rated | not rated | not rated | not rated | not rated |
| 40 | 185.00 | 107.55 | not rated | not rated | not rated | not rated |
| 45 | 260.94 | 184.85 | 107.89 | not rated | not rated | not rated |
| 50 | 336.25 | 260.31 | 184.74 | 108.22 | not rated | not rated |
| 55 | 411.27 | 335.16 | 259.79 | 184.71 | 108.58 | not rated |
| 60 | 486.12 | 409.72 | 334.25 | 259.44 | 184.81 | 108.99 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 90.89 | not rated | not rated | not rated | not rated | not rated |
| 40 | 155.77 | 91.20 | not rated | not rated | not rated | not rated |
| 45 | 218.91 | 155.59 | 91.47 | not rated | not rated | not rated |
| 50 | 281.46 | 218.28 | 155.45 | 91.73 | not rated | not rated |
| 55 | 343.74 | 280.44 | 217.79 | 155.40 | 92.03 | not rated |
| 60 | 405.89 | 342.34 | 279.60 | 217.45 | 155.45 | 92.38 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 185.003 | 32.11 | 86.6 |
| Low speed (Y) | 155.772 | 27.03 | 63.8 |
| A | 4850 mm |
|---|---|
| B | 1220 mm |
| C | 1230 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 4600 mm |
| H | 900 mm |
| I | 1180 mm |
| K | 5100 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4850 mm |
|---|---|
| Width | 1230 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.