BC/BD-2X650BD5-B09 C
259.16 kW
Defrost: None
Product code: BC/BD-t-680GB5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 98,339 m³/h |
|---|---|
| External surface | 413.8 m² |
| Inner volume | 69.0 dm³ |
| Fin material | Aluminium |
| Net weight | 842 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 89.5 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-t-680GB5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 144.36 | not rated | not rated | not rated | not rated | not rated |
| 40 | 259.29 | 145.91 | not rated | not rated | not rated | not rated |
| 45 | 371.58 | 260.29 | 147.30 | not rated | not rated | not rated |
| 50 | 483.06 | 372.16 | 261.24 | 148.56 | not rated | not rated |
| 55 | 594.15 | 483.27 | 372.81 | 262.23 | 149.78 | not rated |
| 60 | 705.02 | 594.00 | 483.63 | 373.60 | 263.32 | 151.01 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 116.87 | not rated | not rated | not rated | not rated | not rated |
| 40 | 208.20 | 118.12 | not rated | not rated | not rated | not rated |
| 45 | 297.03 | 208.95 | 119.25 | not rated | not rated | not rated |
| 50 | 385.10 | 297.42 | 209.69 | 120.29 | not rated | not rated |
| 55 | 472.79 | 385.16 | 297.90 | 210.48 | 121.30 | not rated |
| 60 | 560.28 | 472.56 | 385.40 | 298.53 | 211.38 | 122.34 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 259.288 | 45.00 | 33.0 |
| Low speed (Y) | 208.195 | 36.14 | 22.3 |
| A | 6650 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 6400 mm |
| H | 1050 mm |
| I | 1180 mm |
| K | 6950 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 6650 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.