BE-191CB5-B04 C
102.63 kW
Defrost: None
Product code: BE-180CD1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 22,273 m³/h |
|---|---|
| External surface | 941.3 m² |
| Inner volume | 106.5 dm³ |
| Fin material | Aluminium |
| Net weight | 579 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 1,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BE-180CD1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 63.94 | not rated | not rated | not rated | not rated | not rated |
| 40 | 102.11 | 63.55 | not rated | not rated | not rated | not rated |
| 45 | 139.16 | 101.25 | 63.21 | not rated | not rated | not rated |
| 50 | 175.85 | 137.87 | 100.50 | 62.93 | not rated | not rated |
| 55 | 212.38 | 174.15 | 136.75 | 99.87 | 62.72 | not rated |
| 60 | 248.83 | 210.28 | 172.67 | 135.81 | 99.41 | 62.62 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 48.88 | not rated | not rated | not rated | not rated | not rated |
| 40 | 77.31 | 48.56 | not rated | not rated | not rated | not rated |
| 45 | 104.90 | 76.62 | 48.27 | not rated | not rated | not rated |
| 50 | 132.24 | 103.88 | 76.01 | 48.03 | not rated | not rated |
| 55 | 159.46 | 130.90 | 102.99 | 75.51 | 47.86 | not rated |
| 60 | 186.61 | 157.81 | 129.73 | 102.25 | 75.14 | 47.77 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 102.109 | 17.71 | 64.4 |
| Low speed (Y) | 77.312 | 13.41 | 39.2 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 2860 mm |
| F | 1050 mm |
| G | 3460 mm |
| E1 | 2430 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 3460 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.