BE-180CD1-B01 C
102.11 kW
Defrost: None
Product code: BE-191CB5-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 30,158 m³/h |
|---|---|
| External surface | 477.6 m² |
| Inner volume | 67.6 dm³ |
| Fin material | Aluminium |
| Net weight | 466 kg |
| Quantity | 1 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 2,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | D |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BE-191CB5-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 60.95 | not rated | not rated | not rated | not rated | not rated |
| 40 | 102.63 | 60.88 | not rated | not rated | not rated | not rated |
| 45 | 143.33 | 102.22 | 60.82 | not rated | not rated | not rated |
| 50 | 183.73 | 142.62 | 101.87 | 60.77 | not rated | not rated |
| 55 | 223.96 | 182.69 | 141.98 | 101.56 | 60.75 | not rated |
| 60 | 264.12 | 222.63 | 181.78 | 141.44 | 101.35 | 60.78 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 49.37 | not rated | not rated | not rated | not rated | not rated |
| 40 | 82.49 | 49.28 | not rated | not rated | not rated | not rated |
| 45 | 114.77 | 82.10 | 49.21 | not rated | not rated | not rated |
| 50 | 146.79 | 114.12 | 81.76 | 49.14 | not rated | not rated |
| 55 | 178.68 | 145.87 | 113.54 | 81.49 | 49.11 | not rated |
| 60 | 210.50 | 177.50 | 145.06 | 113.06 | 81.28 | 49.13 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 102.626 | 17.81 | 83.5 |
| Low speed (Y) | 82.489 | 14.32 | 56.7 |
| A | 1958 mm |
|---|---|
| B | 1210 mm |
| C | 2860 mm |
| F | 1050 mm |
| G | 3460 mm |
| E1 | 2430 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 3460 mm |
|---|---|
| Width | 1210 mm |
| Height | 1958 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.