BE-191DC5-B04 C
98.37 kW
Defrost: None
Product code: BE-180CD5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 22,356 m³/h |
|---|---|
| External surface | 795.9 m² |
| Inner volume | 106.5 dm³ |
| Fin material | Aluminium |
| Net weight | 557 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 1,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BE-180CD5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 61.13 | not rated | not rated | not rated | not rated | not rated |
| 40 | 98.62 | 60.81 | not rated | not rated | not rated | not rated |
| 45 | 135.03 | 97.87 | 60.53 | not rated | not rated | not rated |
| 50 | 171.09 | 133.88 | 97.20 | 60.29 | not rated | not rated |
| 55 | 207.00 | 169.56 | 132.87 | 96.65 | 60.13 | not rated |
| 60 | 242.82 | 205.09 | 168.21 | 132.03 | 96.24 | 60.05 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 47.16 | not rated | not rated | not rated | not rated | not rated |
| 40 | 75.35 | 46.88 | not rated | not rated | not rated | not rated |
| 45 | 102.70 | 74.72 | 46.64 | not rated | not rated | not rated |
| 50 | 129.80 | 101.77 | 74.18 | 46.44 | not rated | not rated |
| 55 | 156.78 | 128.57 | 100.95 | 73.73 | 46.29 | not rated |
| 60 | 183.70 | 155.25 | 127.49 | 100.27 | 73.39 | 46.22 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 98.615 | 17.10 | 60.5 |
| Low speed (Y) | 75.345 | 13.07 | 37.5 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 2860 mm |
| F | 1050 mm |
| G | 3460 mm |
| E1 | 2430 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 3460 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.