Skip to Content

Dry cooler BE-180DB5-B01 C

Dry cooler BE-180DB5-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-180DB5-B01 C

Heat rejection i
69.30 kW
Air flow
22,400 m³/h
Fans
1 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 22,400 m³/h
External surface 268.8 m²
Inner volume 39.9 dm³
Fin materialAluminium
Net weight 367 kg
Fans
Quantity 1
Diameter 800 mm
Speed 900 rpm
Power 1,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 48.0 dB(A)
Sound power 80.1 dB(A)
Energy class D
Connections
Inlet 1 1/2"
Outlet 1 1/2"
Defrost
BE-180DB5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
69.301 kW Fluid flow 12.03 m³/h Pressure drop 39.7 kPa
Heat rejection · Low speed (Y)
55.226 kW Fluid flow 9.58 m³/h Pressure drop 26.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 40.46 not rated not rated not rated not rated not rated
40 69.30 40.53 not rated not rated not rated not rated
45 97.43 69.14 40.58 not rated not rated not rated
50 125.34 97.07 68.99 40.63 not rated not rated
55 153.14 124.78 96.74 68.87 40.68 not rated
60 180.89 152.39 124.28 96.47 68.79 40.76

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 32.43 not rated not rated not rated not rated not rated
40 55.23 32.48 not rated not rated not rated not rated
45 77.40 55.07 32.51 not rated not rated not rated
50 99.37 77.06 54.92 32.54 not rated not rated
55 121.26 98.87 76.76 54.80 32.58 not rated
60 143.08 120.59 98.42 76.52 54.73 32.64

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 69.301 12.03 39.7
Low speed (Y) 55.226 9.58 26.6

Dimensions

Dimension drawing of BE-180DB5-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 2260 mm
F 1050 mm
G 2860 mm
E1 1830 mm
D IN 1 1/2"
D OUT 1 1/2"
Overall [mm]
Length 2860 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.