BE-191DD1-B04 C
115.69 kW
Defrost: None
Product code: BE-191CC5-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 29,887 m³/h |
|---|---|
| External surface | 636.8 m² |
| Inner volume | 87.0 dm³ |
| Fin material | Aluminium |
| Net weight | 514 kg |
| Quantity | 1 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 2,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | D |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BE-191CC5-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 69.85 | not rated | not rated | not rated | not rated | not rated |
| 40 | 115.89 | 69.69 | not rated | not rated | not rated | not rated |
| 45 | 160.73 | 115.29 | 69.54 | not rated | not rated | not rated |
| 50 | 205.17 | 159.72 | 114.76 | 69.43 | not rated | not rated |
| 55 | 249.41 | 203.76 | 158.83 | 114.32 | 69.34 | not rated |
| 60 | 293.56 | 247.62 | 202.52 | 158.09 | 114.00 | 69.35 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 55.66 | not rated | not rated | not rated | not rated | not rated |
| 40 | 91.57 | 55.50 | not rated | not rated | not rated | not rated |
| 45 | 126.45 | 91.02 | 55.35 | not rated | not rated | not rated |
| 50 | 160.99 | 125.56 | 90.54 | 55.22 | not rated | not rated |
| 55 | 195.38 | 159.77 | 124.78 | 90.14 | 55.15 | not rated |
| 60 | 229.68 | 193.83 | 158.70 | 124.13 | 89.86 | 55.14 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 115.894 | 20.10 | 66.3 |
| Low speed (Y) | 91.568 | 15.88 | 43.5 |
| A | 1958 mm |
|---|---|
| B | 1210 mm |
| C | 2860 mm |
| F | 1050 mm |
| G | 3460 mm |
| E1 | 2430 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 3460 mm |
|---|---|
| Width | 1210 mm |
| Height | 1958 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.