BE-t-191HC1-B04 C
125.47 kW
Defrost: None
Product code: BE-191CD5-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 29,613 m³/h |
|---|---|
| External surface | 795.9 m² |
| Inner volume | 106.5 dm³ |
| Fin material | Aluminium |
| Net weight | 562 kg |
| Quantity | 1 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 2,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | D |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BE-191CD5-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 76.97 | not rated | not rated | not rated | not rated | not rated |
| 40 | 125.28 | 76.64 | not rated | not rated | not rated | not rated |
| 45 | 172.27 | 124.45 | 76.35 | not rated | not rated | not rated |
| 50 | 218.83 | 170.97 | 123.71 | 76.11 | not rated | not rated |
| 55 | 265.19 | 217.07 | 169.83 | 123.11 | 75.95 | not rated |
| 60 | 311.44 | 262.98 | 215.53 | 168.88 | 122.67 | 75.89 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 60.49 | not rated | not rated | not rated | not rated | not rated |
| 40 | 97.54 | 60.19 | not rated | not rated | not rated | not rated |
| 45 | 133.52 | 96.82 | 59.93 | not rated | not rated | not rated |
| 50 | 169.17 | 132.43 | 96.20 | 59.71 | not rated | not rated |
| 55 | 204.66 | 167.71 | 131.47 | 95.68 | 59.56 | not rated |
| 60 | 240.06 | 202.84 | 166.43 | 130.69 | 95.31 | 59.51 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 125.281 | 21.73 | 92.5 |
| Low speed (Y) | 97.536 | 16.92 | 59.3 |
| A | 1958 mm |
|---|---|
| B | 1210 mm |
| C | 2860 mm |
| F | 1050 mm |
| G | 3460 mm |
| E1 | 2430 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 3460 mm |
|---|---|
| Width | 1210 mm |
| Height | 1958 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.