Skip to Content

Dry cooler BE-191DB1-B04 C

Dry cooler BE-191DB1-B04 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-191DB1-B04 C

Heat rejection i
92.93 kW
Air flow
29,550 m³/h
Fans
1 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 29,550 m³/h
External surface 317.3 m²
Inner volume 39.9 dm³
Fin materialAluminium
Net weight 379 kg
Fans
Quantity 1
Diameter 910 mm
Speed 840 rpm
Power 2,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 58.0 dB(A)
Sound power 90.0 dB(A)
Energy class E
Connections
Inlet 1 1/2"
Outlet 1 1/2"
Defrost
BE-191DB1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
92.933 kW Fluid flow 16.13 m³/h Pressure drop 66.9 kPa
Heat rejection · Low speed (Y)
74.702 kW Fluid flow 12.97 m³/h Pressure drop 45.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 54.31 not rated not rated not rated not rated not rated
40 92.93 54.40 not rated not rated not rated not rated
45 130.63 92.72 54.46 not rated not rated not rated
50 168.04 130.15 92.52 54.52 not rated not rated
55 205.31 167.31 129.73 92.37 54.60 not rated
60 242.51 204.33 166.66 129.39 92.29 54.70

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 43.94 not rated not rated not rated not rated not rated
40 74.70 44.00 not rated not rated not rated not rated
45 104.65 74.49 44.03 not rated not rated not rated
50 134.35 104.21 74.30 44.07 not rated not rated
55 163.91 133.68 103.82 74.15 44.12 not rated
60 193.42 163.04 133.10 103.50 74.06 44.20

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 92.933 16.13 66.9
Low speed (Y) 74.702 12.97 45.4

Dimensions

Dimension drawing of BE-191DB1-B04 C
Dimension drawing
Dimensions as drawn
A 1958 mm
B 1210 mm
C 2260 mm
F 1050 mm
G 2860 mm
E1 1830 mm
D IN 1 1/2"
D OUT 1 1/2"
Overall [mm]
Length 2860 mm
Width 1210 mm
Height 1958 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.