BE-180DD1-B01 C
92.15 kW
Defrost: None
Product code: BE-180CC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 22,503 m³/h |
|---|---|
| External surface | 636.8 m² |
| Inner volume | 87.0 dm³ |
| Fin material | Aluminium |
| Net weight | 509 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 1,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 80.2 dB(A) |
| Energy class | D |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BE-180CC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 56.03 | not rated | not rated | not rated | not rated | not rated |
| 40 | 92.20 | 55.86 | not rated | not rated | not rated | not rated |
| 45 | 127.34 | 91.64 | 55.70 | not rated | not rated | not rated |
| 50 | 162.14 | 126.42 | 91.13 | 55.56 | not rated | not rated |
| 55 | 196.78 | 160.87 | 125.60 | 90.71 | 55.47 | not rated |
| 60 | 231.33 | 195.18 | 159.76 | 124.93 | 90.41 | 55.45 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 43.83 | not rated | not rated | not rated | not rated | not rated |
| 40 | 71.45 | 43.67 | not rated | not rated | not rated | not rated |
| 45 | 98.24 | 70.97 | 43.51 | not rated | not rated | not rated |
| 50 | 124.76 | 97.46 | 70.53 | 43.39 | not rated | not rated |
| 55 | 151.15 | 123.70 | 96.78 | 70.17 | 43.31 | not rated |
| 60 | 177.47 | 149.82 | 122.78 | 96.21 | 69.91 | 43.28 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 92.200 | 15.99 | 44.1 |
| Low speed (Y) | 71.452 | 12.39 | 28.0 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 2860 mm |
| F | 1050 mm |
| G | 3460 mm |
| E1 | 2430 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 3460 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.