BE-180DD5-B01 C
87.51 kW
Defrost: None
Product code: BE-180CB1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 22,602 m³/h |
|---|---|
| External surface | 564.8 m² |
| Inner volume | 67.6 dm³ |
| Fin material | Aluminium |
| Net weight | 474 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 1,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 80.2 dB(A) |
| Energy class | D |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BE-180CB1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 53.48 | not rated | not rated | not rated | not rated | not rated |
| 40 | 88.60 | 53.34 | not rated | not rated | not rated | not rated |
| 45 | 122.80 | 88.11 | 53.21 | not rated | not rated | not rated |
| 50 | 156.68 | 121.98 | 87.67 | 53.09 | not rated | not rated |
| 55 | 190.42 | 155.55 | 121.26 | 87.31 | 53.02 | not rated |
| 60 | 224.07 | 188.97 | 154.55 | 120.65 | 87.04 | 53.01 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 42.14 | not rated | not rated | not rated | not rated | not rated |
| 40 | 69.21 | 42.00 | not rated | not rated | not rated | not rated |
| 45 | 95.50 | 68.77 | 41.87 | not rated | not rated | not rated |
| 50 | 121.53 | 94.79 | 68.39 | 41.77 | not rated | not rated |
| 55 | 147.44 | 120.56 | 94.17 | 68.07 | 41.70 | not rated |
| 60 | 173.29 | 146.22 | 119.71 | 93.65 | 67.83 | 41.68 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 88.600 | 15.36 | 64.3 |
| Low speed (Y) | 69.206 | 12.00 | 41.5 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 2860 mm |
| F | 1050 mm |
| G | 3460 mm |
| E1 | 2430 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 3460 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.