Skip to Content

Dry cooler BE-180DC1-B01 C

Dry cooler BE-180DC1-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-180DC1-B01 C

Heat rejection i
86.06 kW
Air flow
22,072 m³/h
Fans
1 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 22,072 m³/h
External surface 423.0 m²
Inner volume 50.2 dm³
Fin materialAluminium
Net weight 404 kg
Fans
Quantity 1
Diameter 800 mm
Speed 900 rpm
Power 1,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 48.0 dB(A)
Sound power 80.0 dB(A)
Energy class D
Connections
Inlet 1 1/2"
Outlet 1 1/2"
Defrost
BE-180DC1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
86.061 kW Fluid flow 14.92 m³/h Pressure drop 76.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
66.740 kW Fluid flow 11.57 m³/h Pressure drop 48.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 51.96 not rated not rated not rated not rated not rated
40 86.06 51.85 not rated not rated not rated not rated
45 119.25 85.62 51.74 not rated not rated not rated
50 152.14 118.51 85.22 51.64 not rated not rated
55 184.89 151.10 117.85 84.90 51.60 not rated
60 217.56 183.57 150.19 117.31 84.67 51.61

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 40.62 not rated not rated not rated not rated not rated
40 66.74 40.51 not rated not rated not rated not rated
45 92.10 66.36 40.41 not rated not rated not rated
50 117.22 91.47 66.02 40.33 not rated not rated
55 142.22 116.35 90.92 65.74 40.28 not rated
60 167.16 141.12 115.60 90.47 65.55 40.28

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 86.061 14.92 76.3
Low speed (Y) 66.740 11.57 48.6

Dimensions

Dimension drawing of BE-180DC1-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 2260 mm
F 1050 mm
G 2860 mm
E1 1830 mm
D IN 1 1/2"
D OUT 1 1/2"
Overall [mm]
Length 2860 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.