BE-180CB1-B01 C
88.60 kW
Defrost: None
Product code: BE-180DD5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 21,951 m³/h |
|---|---|
| External surface | 447.8 m² |
| Inner volume | 60.0 dm³ |
| Fin material | Aluminium |
| Net weight | 423 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 1,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BE-180DD5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 53.00 | not rated | not rated | not rated | not rated | not rated |
| 40 | 87.51 | 52.88 | not rated | not rated | not rated | not rated |
| 45 | 121.05 | 87.04 | 52.76 | not rated | not rated | not rated |
| 50 | 154.28 | 120.27 | 86.62 | 52.66 | not rated | not rated |
| 55 | 187.37 | 153.20 | 119.58 | 86.28 | 52.61 | not rated |
| 60 | 220.37 | 185.99 | 152.25 | 119.01 | 86.03 | 52.62 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 41.25 | not rated | not rated | not rated | not rated | not rated |
| 40 | 67.56 | 41.14 | not rated | not rated | not rated | not rated |
| 45 | 93.08 | 67.16 | 41.04 | not rated | not rated | not rated |
| 50 | 118.34 | 92.43 | 66.81 | 40.95 | not rated | not rated |
| 55 | 143.48 | 117.44 | 91.85 | 66.52 | 40.91 | not rated |
| 60 | 168.57 | 142.35 | 116.66 | 91.38 | 66.32 | 40.91 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 87.509 | 15.18 | 55.8 |
| Low speed (Y) | 67.561 | 11.72 | 35.2 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 2260 mm |
| F | 1050 mm |
| G | 2860 mm |
| E1 | 1830 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 2860 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.