BE-180CC5-B01 C
92.20 kW
Defrost: None
Product code: BE-191DB1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 29,550 m³/h |
|---|---|
| External surface | 317.3 m² |
| Inner volume | 39.9 dm³ |
| Fin material | Aluminium |
| Net weight | 379 kg |
| Quantity | 1 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 2,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | E |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BE-191DB1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 54.31 | not rated | not rated | not rated | not rated | not rated |
| 40 | 92.93 | 54.40 | not rated | not rated | not rated | not rated |
| 45 | 130.63 | 92.72 | 54.46 | not rated | not rated | not rated |
| 50 | 168.04 | 130.15 | 92.52 | 54.52 | not rated | not rated |
| 55 | 205.31 | 167.31 | 129.73 | 92.37 | 54.60 | not rated |
| 60 | 242.51 | 204.33 | 166.66 | 129.39 | 92.29 | 54.70 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 43.94 | not rated | not rated | not rated | not rated | not rated |
| 40 | 74.70 | 44.00 | not rated | not rated | not rated | not rated |
| 45 | 104.65 | 74.49 | 44.03 | not rated | not rated | not rated |
| 50 | 134.35 | 104.21 | 74.30 | 44.07 | not rated | not rated |
| 55 | 163.91 | 133.68 | 103.82 | 74.15 | 44.12 | not rated |
| 60 | 193.42 | 163.04 | 133.10 | 103.50 | 74.06 | 44.20 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 92.933 | 16.13 | 66.9 |
| Low speed (Y) | 74.702 | 12.97 | 45.4 |
| A | 1958 mm |
|---|---|
| B | 1210 mm |
| C | 2260 mm |
| F | 1050 mm |
| G | 2860 mm |
| E1 | 1830 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 2860 mm |
|---|---|
| Width | 1210 mm |
| Height | 1958 mm |
Our engineers answer with a selection for your conditions.