BE-2x180CB5-B01T C
160.47 kW
Defrost: None
Product code: BE-280AC1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 42,157 m³/h |
|---|---|
| External surface | 752.7 m² |
| Inner volume | 91.4 dm³ |
| Fin material | Aluminium |
| Net weight | 645 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-280AC1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 95.08 | not rated | not rated | not rated | not rated | not rated |
| 40 | 159.94 | 95.12 | not rated | not rated | not rated | not rated |
| 45 | 222.99 | 159.38 | 95.13 | not rated | not rated | not rated |
| 50 | 285.44 | 221.90 | 158.88 | 95.17 | not rated | not rated |
| 55 | 347.60 | 283.84 | 220.95 | 158.51 | 95.25 | not rated |
| 60 | 409.60 | 345.50 | 282.45 | 220.20 | 158.29 | 95.41 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 74.69 | not rated | not rated | not rated | not rated | not rated |
| 40 | 124.35 | 74.65 | not rated | not rated | not rated | not rated |
| 45 | 172.49 | 123.82 | 74.62 | not rated | not rated | not rated |
| 50 | 220.11 | 171.52 | 123.36 | 74.62 | not rated | not rated |
| 55 | 267.50 | 218.72 | 170.68 | 123.01 | 74.66 | not rated |
| 60 | 314.75 | 265.69 | 217.52 | 170.02 | 122.81 | 74.79 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 159.936 | 27.73 | 52.6 |
| Low speed (Y) | 124.354 | 21.57 | 33.6 |
| A | 1808 mm |
|---|---|
| B | 1150 mm |
| C | 2860 mm |
| F | 1050 mm |
| G | 3460 mm |
| E1 | 1230 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3460 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |