BE-2x180CB5-B01T C
160.47 kW
Defrost: None
Product code: BE-280DC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 44,346 m³/h |
|---|---|
| External surface | 716.8 m² |
| Inner volume | 96.8 dm³ |
| Fin material | Aluminium |
| Net weight | 724 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-280DC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 96.32 | not rated | not rated | not rated | not rated | not rated |
| 40 | 160.97 | 96.19 | not rated | not rated | not rated | not rated |
| 45 | 223.96 | 160.27 | 96.07 | not rated | not rated | not rated |
| 50 | 286.43 | 222.74 | 159.62 | 95.97 | not rated | not rated |
| 55 | 348.65 | 284.70 | 221.66 | 159.11 | 95.92 | not rated |
| 60 | 410.73 | 346.43 | 283.18 | 220.77 | 158.75 | 95.97 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 75.99 | not rated | not rated | not rated | not rated | not rated |
| 40 | 126.05 | 75.86 | not rated | not rated | not rated | not rated |
| 45 | 174.74 | 125.43 | 75.73 | not rated | not rated | not rated |
| 50 | 222.98 | 173.69 | 124.88 | 75.62 | not rated | not rated |
| 55 | 271.02 | 221.51 | 172.76 | 124.43 | 75.56 | not rated |
| 60 | 318.94 | 269.14 | 220.22 | 171.99 | 124.11 | 75.58 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 160.972 | 27.94 | 65.1 |
| Low speed (Y) | 126.051 | 21.86 | 42.1 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 4060 mm |
| F | 1050 mm |
| G | 4660 mm |
| E1 | 1830 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 4660 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.