Skip to Content

Dry cooler BE-280AC1-B01 C

Dry cooler BE-280AC1-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-280AC1-B01 C

Heat rejection i
159.94 kW
Air flow
42,157 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BE — BE = V-type dry cooler.
  • D
    Number of fans per row: 2 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 80 — Ø800 mm
  • G
    Coil tube rows (2nd dimensional letter): C — 4 tube rows
  • H
    Fin spacing: 1 — 2.1 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 01 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)

Data

Coil
Air flow 42,157 m³/h
External surface 752.7 m²
Inner volume 91.4 dm³
Fin materialAluminium
Net weight 645 kg
Fans
Quantity 2
Diameter 800 mm
Speed 900 rpm
Power 3,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 51.0 dB(A)
Sound power 83.0 dB(A)
Energy class D
Connections
Inlet 2"
Outlet 2"
Defrost
BE-280AC1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
159.936 kW Fluid flow 27.73 m³/h Pressure drop 52.6 kPa
Heat rejection · Low speed (Y)
124.354 kW Fluid flow 21.57 m³/h Pressure drop 33.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 95.08 not rated not rated not rated not rated not rated
40 159.94 95.12 not rated not rated not rated not rated
45 222.99 159.38 95.13 not rated not rated not rated
50 285.44 221.90 158.88 95.17 not rated not rated
55 347.60 283.84 220.95 158.51 95.25 not rated
60 409.60 345.50 282.45 220.20 158.29 95.41

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 74.69 not rated not rated not rated not rated not rated
40 124.35 74.65 not rated not rated not rated not rated
45 172.49 123.82 74.62 not rated not rated not rated
50 220.11 171.52 123.36 74.62 not rated not rated
55 267.50 218.72 170.68 123.01 74.66 not rated
60 314.75 265.69 217.52 170.02 122.81 74.79

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 159.936 27.73 52.6
Low speed (Y) 124.354 21.57 33.6

Dimensions

Dimension drawing of BE-280AC1-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1150 mm
C 2860 mm
F 1050 mm
G 3460 mm
E1 1230 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 3460 mm
Width 1210 mm
Height 1808 mm

Downloads