Skip to Content

Dry cooler BE-280AD5-B01 C

Dry cooler BE-280AD5-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-280AD5-B01 C

Heat rejection i
164.22 kW
Air flow
41,682 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 41,682 m³/h
External surface 795.9 m²
Inner volume 112.1 dm³
Fin materialAluminium
Net weight 677 kg
Fans
Quantity 2
Diameter 800 mm
Speed 900 rpm
Power 3,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 51.0 dB(A)
Sound power 83.0 dB(A)
Energy class D
Connections
Inlet 2"
Outlet 2"
Defrost
BE-280AD5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
164.223 kW Fluid flow 28.48 m³/h Pressure drop 77.4 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
126.736 kW Fluid flow 21.98 m³/h Pressure drop 48.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 99.16 not rated not rated not rated not rated not rated
40 164.22 99.01 not rated not rated not rated not rated
45 227.55 163.49 98.87 not rated not rated not rated
50 290.30 226.30 162.86 98.76 not rated not rated
55 352.78 288.54 225.21 162.37 98.74 not rated
60 415.12 350.52 287.02 224.36 162.06 98.84

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 77.30 not rated not rated not rated not rated not rated
40 126.74 77.15 not rated not rated not rated not rated
45 174.74 126.12 77.03 not rated not rated not rated
50 222.26 173.70 125.60 76.94 not rated not rated
55 269.57 220.83 172.83 125.20 76.93 not rated
60 316.76 267.75 219.61 172.15 124.96 76.99

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 164.223 28.48 77.4
Low speed (Y) 126.736 21.98 48.9

Dimensions

Dimension drawing of BE-280AD5-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 2860 mm
F 1050 mm
G 3460 mm
E1 1230 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 3460 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.