BE-280AD5-B01 C
164.22 kW
Defrost: None
Product code: BE-2x191DB5-B04T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 58,987 m³/h |
|---|---|
| External surface | 492.5 m² |
| Inner volume | 79.7 dm³ |
| Fin material | Aluminium |
| Net weight | 919 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-2x191DB5-B04T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 95.26 | not rated | not rated | not rated | not rated | not rated |
| 40 | 164.28 | 95.49 | not rated | not rated | not rated | not rated |
| 45 | 231.81 | 164.05 | 95.68 | not rated | not rated | not rated |
| 50 | 298.85 | 231.17 | 163.84 | 95.84 | not rated | not rated |
| 55 | 365.69 | 297.82 | 230.61 | 163.69 | 96.03 | not rated |
| 60 | 432.40 | 364.28 | 296.92 | 230.16 | 163.62 | 96.25 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 77.77 | not rated | not rated | not rated | not rated | not rated |
| 40 | 133.38 | 77.94 | not rated | not rated | not rated | not rated |
| 45 | 187.66 | 133.13 | 78.07 | not rated | not rated | not rated |
| 50 | 241.52 | 187.06 | 132.92 | 78.19 | not rated | not rated |
| 55 | 295.18 | 240.57 | 186.52 | 132.75 | 78.33 | not rated |
| 60 | 348.74 | 293.90 | 239.73 | 186.10 | 132.66 | 78.51 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 164.281 | 28.51 | 66.5 |
| Low speed (Y) | 133.383 | 23.15 | 45.9 |
| A | 2910 mm |
|---|---|
| B | 2400 mm |
| C | 2250 mm |
| F | 2330 mm |
| G | 2850 mm |
| E1 | 1850 mm |
| H | 2500 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2850 mm |
|---|---|
| Width | 2400 mm |
| Height | 2910 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.