Skip to Content

Dry cooler BE-280BB5-B01 C

Dry cooler BE-280BB5-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-280BB5-B01 C

Heat rejection i
115.15 kW
Air flow
43,100 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 43,100 m³/h
External surface 328.3 m²
Inner volume 46.2 dm³
Fin materialAluminium
Net weight 527 kg
Fans
Quantity 2
Diameter 800 mm
Speed 900 rpm
Power 3,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 51.0 dB(A)
Sound power 83.0 dB(A)
Energy class E
Connections
Inlet 1 1/2"
Outlet 1 1/2"
Defrost
BE-280BB5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
115.150 kW Fluid flow 19.98 m³/h Pressure drop 44.6 kPa
Heat rejection · Low speed (Y)
92.582 kW Fluid flow 16.07 m³/h Pressure drop 30.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 65.90 not rated not rated not rated not rated not rated
40 115.15 66.20 not rated not rated not rated not rated
45 163.29 115.12 66.46 not rated not rated not rated
50 211.08 162.97 115.10 66.69 not rated not rated
55 258.71 210.50 162.71 115.09 66.91 not rated
60 306.25 257.87 209.99 162.50 115.14 67.14

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 53.27 not rated not rated not rated not rated not rated
40 92.58 53.51 not rated not rated not rated not rated
45 130.88 92.52 53.71 not rated not rated not rated
50 168.86 130.57 92.47 53.90 not rated not rated
55 206.70 168.32 130.30 92.44 54.07 not rated
60 244.46 205.94 167.86 130.11 92.47 54.26

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 115.150 19.98 44.6
Low speed (Y) 92.582 16.07 30.2

Dimensions

Dimension drawing of BE-280BB5-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 2660 mm
F 1050 mm
G 3260 mm
E1 1130 mm
D IN 1 1/2"
D OUT 1 1/2"
Overall [mm]
Length 3260 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.