Skip to Content

Dry cooler BE-2X380BC1-B01C C

Dry cooler BE-2X380BC1-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2X380BC1-B01C C

Heat rejection i
392.61 kW
Air flow
118,484 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 118,484 m³/h
External surface 1,199.3 m²
Inner volume 162.5 dm³
Fin materialAluminium
Net weight 1,627 kg
Fans
Quantity 6
Diameter 800 mm
Speed 900 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 88.0 dB(A)
Energy class D
Connections
Inlet 3"
Outlet 3"
Defrost
BE-2X380BC1-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
392.607 kW Fluid flow 68.13 m³/h Pressure drop 62.7 kPa
Heat rejection · Low speed (Y)
305.652 kW Fluid flow 53.04 m³/h Pressure drop 40.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 229.35 not rated not rated not rated not rated not rated
40 392.61 230.07 not rated not rated not rated not rated
45 551.75 392.20 230.72 not rated not rated not rated
50 709.53 550.36 391.91 231.34 not rated not rated
55 866.68 707.22 549.25 391.80 232.03 not rated
60 1023.46 863.42 705.32 548.51 392.01 232.87

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 180.05 not rated not rated not rated not rated not rated
40 305.65 180.58 not rated not rated not rated not rated
45 427.65 305.21 181.05 not rated not rated not rated
50 548.52 426.38 304.84 181.51 not rated not rated
55 668.85 546.50 425.38 304.70 182.07 not rated
60 788.88 666.09 544.85 424.72 304.83 182.75

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 392.607 68.13 62.7
Low speed (Y) 305.652 53.04 40.2

Dimensions

Dimension drawing of BE-2X380BC1-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 3750 mm
F 2230 mm
G 4350 mm
E1 1150 mm
E2 1100 mm
H 4000 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 4350 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.