BE-2X380BC1-B01C C
392.61 kW
Defrost: None
Product code: BE-680AB5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 130,190 m³/h |
|---|---|
| External surface | 1,432.7 m² |
| Inner volume | 209.6 dm³ |
| Fin material | Aluminium |
| Net weight | 1,603 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-680AB5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 227.97 | not rated | not rated | not rated | not rated | not rated |
| 40 | 392.32 | 228.47 | not rated | not rated | not rated | not rated |
| 45 | 553.01 | 391.64 | 228.85 | not rated | not rated | not rated |
| 50 | 712.53 | 551.28 | 391.05 | 229.22 | not rated | not rated |
| 55 | 871.48 | 709.78 | 549.78 | 390.60 | 229.64 | not rated |
| 60 | 1030.15 | 867.76 | 707.37 | 548.57 | 390.39 | 230.17 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 184.65 | not rated | not rated | not rated | not rated | not rated |
| 40 | 315.29 | 184.95 | not rated | not rated | not rated | not rated |
| 45 | 442.70 | 314.56 | 185.20 | not rated | not rated | not rated |
| 50 | 569.06 | 441.05 | 313.93 | 185.44 | not rated | not rated |
| 55 | 694.92 | 566.52 | 439.63 | 313.44 | 185.73 | not rated |
| 60 | 820.51 | 691.54 | 564.33 | 438.48 | 313.20 | 186.14 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 392.320 | 68.09 | 54.7 |
| Low speed (Y) | 315.288 | 54.72 | 37.1 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 7660 mm |
| F | 1050 mm |
| G | 8260 mm |
| E1 | 1230 mm |
| E2 | 1200 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 8260 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.