BE-591BB5-B04 C
363.85 kW
Defrost: None
Product code: BE-2X380BC5-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 120,414 m³/h |
|---|---|
| External surface | 1,015.8 m² |
| Inner volume | 162.5 dm³ |
| Fin material | Aluminium |
| Net weight | 1,600 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-2X380BC5-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 210.75 | not rated | not rated | not rated | not rated | not rated |
| 40 | 363.37 | 211.55 | not rated | not rated | not rated | not rated |
| 45 | 512.38 | 363.20 | 212.26 | not rated | not rated | not rated |
| 50 | 660.25 | 511.39 | 363.12 | 212.88 | not rated | not rated |
| 55 | 807.57 | 658.49 | 510.62 | 363.10 | 213.53 | not rated |
| 60 | 954.62 | 805.08 | 657.05 | 510.04 | 363.29 | 214.29 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 167.18 | not rated | not rated | not rated | not rated | not rated |
| 40 | 286.17 | 167.79 | not rated | not rated | not rated | not rated |
| 45 | 402.00 | 285.93 | 168.33 | not rated | not rated | not rated |
| 50 | 516.81 | 401.06 | 285.78 | 168.84 | not rated | not rated |
| 55 | 631.15 | 515.21 | 400.33 | 285.75 | 169.39 | not rated |
| 60 | 745.25 | 628.94 | 513.93 | 399.85 | 285.96 | 170.05 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 363.366 | 63.06 | 54.6 |
| Low speed (Y) | 286.168 | 49.66 | 35.7 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 3750 mm |
| F | 2230 mm |
| G | 4350 mm |
| E1 | 1150 mm |
| E2 | 1100 mm |
| H | 4000 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4350 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.