Skip to Content

Dry cooler BE-591BB5-B04 C

Dry cooler BE-591BB5-B04 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-591BB5-B04 C

Heat rejection i
363.85 kW
Air flow
142,513 m³/h
Fans
5 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 142,513 m³/h
External surface 896.0 m²
Inner volume 136.7 dm³
Fin materialAluminium
Net weight 1,296 kg
Fans
Quantity 5
Diameter 910 mm
Speed 840 rpm
Power 14,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 65.0 dB(A)
Sound power 97.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BE-591BB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
363.845 kW Fluid flow 63.14 m³/h Pressure drop 102.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
296.849 kW Fluid flow 51.52 m³/h Pressure drop 71.3 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 210.72 not rated not rated not rated not rated not rated
40 363.85 211.28 not rated not rated not rated not rated
45 514.01 363.57 211.74 not rated not rated not rated
50 663.23 513.00 363.34 212.17 not rated not rated
55 812.00 661.51 512.13 363.24 212.63 not rated
60 960.54 809.59 660.04 511.50 363.29 213.17

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 172.89 not rated not rated not rated not rated not rated
40 296.85 173.29 not rated not rated not rated not rated
45 418.18 296.52 173.61 not rated not rated not rated
50 538.67 417.21 296.25 173.96 not rated not rated
55 658.79 537.07 416.38 296.08 174.32 not rated
60 778.68 656.58 535.73 415.77 296.09 174.76

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 363.845 63.14 102.2
Low speed (Y) 296.849 51.52 71.3

Dimensions

Dimension drawing of BE-591BB5-B04 C
Dimension drawing
Dimensions as drawn
A 1958 mm
B 1210 mm
C 6460 mm
F 1050 mm
G 7060 mm
E1 1230 mm
E2 1200 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 7060 mm
Width 1210 mm
Height 1958 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.