BE-2x580BB5-B01C C
522.68 kW
Defrost: None
Product code: BE-2X480AC5-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 162,502 m³/h |
|---|---|
| External surface | 1,948.4 m² |
| Inner volume | 315.7 dm³ |
| Fin material | Aluminium |
| Net weight | 2,250 kg |
| Quantity | 8 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 14,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 89.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-2X480AC5-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 298.31 | not rated | not rated | not rated | not rated | not rated |
| 40 | 522.95 | 300.18 | not rated | not rated | not rated | not rated |
| 45 | 741.23 | 522.91 | 301.77 | not rated | not rated | not rated |
| 50 | 957.48 | 739.63 | 522.89 | 303.18 | not rated | not rated |
| 55 | 1172.80 | 954.45 | 738.31 | 523.05 | 304.57 | not rated |
| 60 | 1387.57 | 1168.35 | 951.87 | 737.40 | 523.54 | 306.10 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 237.45 | not rated | not rated | not rated | not rated | not rated |
| 40 | 412.55 | 238.95 | not rated | not rated | not rated | not rated |
| 45 | 581.85 | 412.38 | 240.20 | not rated | not rated | not rated |
| 50 | 749.35 | 580.38 | 412.27 | 241.34 | not rated | not rated |
| 55 | 915.99 | 746.69 | 579.19 | 412.33 | 242.48 | not rated |
| 60 | 1082.15 | 912.19 | 744.49 | 578.40 | 412.66 | 243.74 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 522.952 | 90.77 | 20.0 |
| Low speed (Y) | 412.549 | 71.59 | 13.0 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 5250 mm |
| F | 2230 mm |
| G | 5850 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| H | 5500 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 5850 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |