Skip to Content

Dry cooler BE-791AB5-B04 C

Dry cooler BE-791AB5-B04 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-791AB5-B04 C

Heat rejection i
524.58 kW
Air flow
198,912 m³/h
Fans
7 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 198,912 m³/h
External surface 1,671.5 m²
Inner volume 262.8 dm³
Fin materialAluminium
Net weight 1,901 kg
Fans
Quantity 7
Diameter 910 mm
Speed 840 rpm
Power 19,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 66.0 dB(A)
Sound power 98.5 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BE-791AB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
524.583 kW Fluid flow 91.05 m³/h Pressure drop 17.4 kPa
Heat rejection · Low speed (Y)
430.175 kW Fluid flow 74.67 m³/h Pressure drop 12.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 291.58 not rated not rated not rated not rated not rated
40 524.58 294.23 not rated not rated not rated not rated
45 751.91 525.42 296.45 not rated not rated not rated
50 977.50 751.30 526.14 298.40 not rated not rated
55 1202.27 975.55 750.78 526.88 300.21 not rated
60 1426.59 1199.03 973.88 750.55 527.77 301.98

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 240.67 not rated not rated not rated not rated not rated
40 430.18 243.38 not rated not rated not rated not rated
45 614.25 430.66 244.62 not rated not rated not rated
50 796.68 613.45 431.08 246.21 not rated not rated
55 978.31 794.68 612.77 431.55 247.69 not rated
60 1159.52 975.18 792.99 612.35 432.20 249.17

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 524.583 91.05 17.4
Low speed (Y) 430.175 74.67 12.1

Dimensions

Dimension drawing of BE-791AB5-B04 C
Dimension drawing
Dimensions as drawn
A 1958 mm
B 1300 mm
C 8860 mm
F 1150 mm
G 9460 mm
E1 1230 mm
E2 1200 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 9460 mm
Width 1300 mm
Height 1958 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.