Skip to Content

Dry cooler BE-780EB1-B01 C

Dry cooler BE-780EB1-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-780EB1-B01 C

Heat rejection i
525.28 kW
Air flow
148,379 m³/h
Fans
7 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 148,379 m³/h
External surface 1,876.5 m²
Inner volume 354.7 dm³
Fin materialAluminium
Net weight 1,966 kg
Fans
Quantity 7
Diameter 800 mm
Speed 900 rpm
Power 12,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 88.5 dB(A)
Energy class D
Connections
Inlet 3"
Outlet 3"
Defrost
BE-780EB1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
525.283 kW Fluid flow 91.17 m³/h Pressure drop 110.6 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
411.484 kW Fluid flow 71.37 m³/h Pressure drop 71.5 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 312.99 not rated not rated not rated not rated not rated
40 525.28 312.79 not rated not rated not rated not rated
45 732.48 523.46 312.59 not rated not rated not rated
50 938.08 729.17 521.89 312.44 not rated not rated
55 1142.90 933.32 726.31 520.53 312.51 not rated
60 1347.32 1136.73 929.21 723.95 519.75 312.84

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 247.43 not rated not rated not rated not rated not rated
40 411.48 247.10 not rated not rated not rated not rated
45 571.38 409.80 246.83 not rated not rated not rated
50 729.90 568.46 408.35 246.66 not rated not rated
55 887.76 725.76 565.93 407.25 246.66 not rated
60 1045.28 882.43 722.18 563.94 406.56 246.87

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 525.283 91.17 110.6
Low speed (Y) 411.484 71.37 71.5

Dimensions

Dimension drawing of BE-780EB1-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 8860 mm
F 1050 mm
G 9460 mm
E1 1230 mm
E2 1200 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 9460 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.