BE-2x580BD1-B01C C
708.99 kW
Defrost: None
Product code: BE-2X580AC5-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 208,995 m³/h |
|---|---|
| External surface | 2,833.5 m² |
| Inner volume | 433.9 dm³ |
| Fin material | Aluminium |
| Net weight | 3,070 kg |
| Quantity | 10 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 18,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-2X580AC5-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 411.85 | not rated | not rated | not rated | not rated | not rated |
| 40 | 708.27 | 413.13 | not rated | not rated | not rated | not rated |
| 45 | 996.68 | 707.08 | 414.24 | not rated | not rated | not rated |
| 50 | 1282.52 | 993.38 | 706.06 | 415.24 | not rated | not rated |
| 55 | 1567.08 | 1277.12 | 990.55 | 705.41 | 416.34 | not rated |
| 60 | 1851.05 | 1559.78 | 1272.54 | 988.31 | 705.27 | 417.71 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 327.81 | not rated | not rated | not rated | not rated | not rated |
| 40 | 558.57 | 328.76 | not rated | not rated | not rated | not rated |
| 45 | 782.24 | 557.33 | 329.56 | not rated | not rated | not rated |
| 50 | 1003.68 | 779.30 | 556.35 | 330.27 | not rated | not rated |
| 55 | 1224.06 | 999.08 | 776.82 | 555.61 | 331.05 | not rated |
| 60 | 1443.85 | 1217.86 | 995.21 | 774.85 | 555.30 | 332.07 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 708.268 | 122.94 | 33.2 |
| Low speed (Y) | 558.569 | 96.94 | 21.7 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 6450 mm |
| F | 2330 mm |
| G | 7050 mm |
| E1 | 1250 mm |
| E2 | 3600 mm |
| H | 6700 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 7050 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.