Skip to Content

Dry cooler BE-2x580BD1-B01C C

Dry cooler BE-2x580BD1-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x580BD1-B01C C

Heat rejection i
708.99 kW
Air flow
190,027 m³/h
Fans
10 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 190,027 m³/h
External surface 2,498.9 m²
Inner volume 321.0 dm³
Fin materialAluminium
Net weight 2,670 kg
Fans
Quantity 10
Diameter 800 mm
Speed 900 rpm
Power 18,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 58.0 dB(A)
Sound power 90.1 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x580BD1-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
708.989 kW Fluid flow 122.96 m³/h Pressure drop 62.9 kPa
Heat rejection · Low speed (Y)
542.195 kW Fluid flow 94.04 m³/h Pressure drop 39.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 421.32 not rated not rated not rated not rated not rated
40 708.99 422.17 not rated not rated not rated not rated
45 988.74 707.75 422.98 not rated not rated not rated
50 1265.84 985.69 706.84 423.72 not rated not rated
55 1541.72 1261.09 983.31 706.18 424.70 not rated
60 1816.92 1535.31 1257.30 981.45 706.25 426.10

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 325.25 not rated not rated not rated not rated not rated
40 542.20 325.71 not rated not rated not rated not rated
45 752.48 540.79 326.03 not rated not rated not rated
50 960.57 749.53 539.68 326.55 not rated not rated
55 1167.65 956.16 747.14 539.03 327.29 not rated
60 1374.18 1161.83 952.58 745.52 539.00 328.39

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 708.989 122.96 62.9
Low speed (Y) 542.195 94.04 39.0

Dimensions

Dimension drawing of BE-2x580BD1-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 5950 mm
F 2230 mm
G 6550 mm
E1 1150 mm
E2 3300 mm
H 6200 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 6550 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.