Skip to Content

Dry cooler BE-2X580BC5-B01T C

Dry cooler BE-2X580BC5-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2X580BC5-B01T C

Heat rejection i
655.26 kW
Air flow
207,688 m³/h
Fans
10 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BE — BE = V-type dry cooler.
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 5 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 80 — Ø800 mm
  • G
    Coil tube rows (2nd dimensional letter): C — 4 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 01 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)
  • K
    Delivery version (optional): T — T: truck delivery version

Data

Coil
Air flow 207,688 m³/h
External surface 2,006.3 m²
Inner volume 321.6 dm³
Fin materialAluminium
Net weight 2,791 kg
Fans
Quantity 10
Diameter 800 mm
Speed 900 rpm
Power 18,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 57.0 dB(A)
Sound power 90.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2X580BC5-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
655.261 kW Fluid flow 113.73 m³/h Pressure drop 59.6 kPa
Heat rejection · Low speed (Y)
516.742 kW Fluid flow 89.68 m³/h Pressure drop 39.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 383.13 not rated not rated not rated not rated not rated
40 655.26 383.98 not rated not rated not rated not rated
45 920.89 654.23 384.70 not rated not rated not rated
50 1184.45 918.20 653.35 385.41 not rated not rated
55 1447.02 1180.17 915.91 652.78 386.26 not rated
60 1709.06 1441.19 1176.52 914.23 652.71 387.31

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 304.33 not rated not rated not rated not rated not rated
40 516.74 304.99 not rated not rated not rated not rated
45 723.51 515.79 305.55 not rated not rated not rated
50 928.39 721.19 515.02 306.12 not rated not rated
55 1132.51 924.78 719.18 514.52 306.82 not rated
60 1336.19 1127.65 921.76 717.81 514.48 307.73

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 655.261 113.73 59.6
Low speed (Y) 516.742 89.68 39.0

Dimensions

Dimension drawing of BE-2X580BC5-B01T C
Dimension drawing
Dimensions as drawn
A 2778 mm
B 2400 mm
C 5950 mm
F 2330 mm
G 6550 mm
E1 1150 mm
E2 3300 mm
H 6200 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 6550 mm
Width 2400 mm
Height 2778 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.