Skip to Content

Dry cooler BE-2X880AC5-B01T C

Dry cooler BE-2X880AC5-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2X880AC5-B01T C

Heat rejection i
1114.43 kW
Air flow
334,393 m³/h
Fans
16 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 334,393 m³/h
External surface 4,533.6 m²
Inner volume 687.1 dm³
Fin materialAluminium
Net weight 4,913 kg
Fans
Quantity 16
Diameter 800 mm
Speed 900 rpm
Power 28,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 60.0 dB(A)
Sound power 93.0 dB(A)
Energy class D
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2X880AC5-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
1114.432 kW Fluid flow 193.41 m³/h Pressure drop 20.7 kPa
Heat rejection · Low speed (Y)
879.759 kW Fluid flow 152.70 m³/h Pressure drop 13.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 637.49 not rated not rated not rated not rated not rated
40 1114.43 641.24 not rated not rated not rated not rated
45 1577.09 1113.72 644.40 not rated not rated not rated
50 2035.15 1572.81 1113.15 647.18 not rated not rated
55 2490.95 2027.31 1569.05 1112.90 649.91 not rated
60 2945.67 2480.01 2020.70 1566.18 1113.42 652.88

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 507.58 not rated not rated not rated not rated not rated
40 879.76 510.62 not rated not rated not rated not rated
45 1238.79 878.85 513.08 not rated not rated not rated
50 1593.79 1234.85 877.93 515.20 not rated not rated
55 1946.88 1587.08 1231.53 877.45 517.26 not rated
60 2298.91 1937.53 1581.45 1228.94 877.48 519.58

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 1114.432 193.41 20.7
Low speed (Y) 879.759 152.70 13.4

Dimensions

Dimension drawing of BE-2X880AC5-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 10050 mm
F 2330 mm
G 10650 mm
E1 1250 mm
E2 2400 mm
H 10300 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 10650 mm
Width 2400 mm
Height 2750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.