Skip to Content

Dry cooler BE-2X980AC1-B01C C

Dry cooler BE-2X980AC1-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2X980AC1-B01C C

Heat rejection i
1272.26 kW
Air flow
360,363 m³/h
Fans
18 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 360,363 m³/h
External surface 5,185.5 m²
Inner volume 704.4 dm³
Fin materialAluminium
Net weight 5,001 kg
Fans
Quantity 18
Diameter 800 mm
Speed 900 rpm
Power 32,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 94.0 dB(A)
Energy class D
Connections
Inlet 6"
Outlet 6"
Defrost
BE-2X980AC1-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
1272.257 kW Fluid flow 220.78 m³/h Pressure drop 29.1 kPa
Heat rejection · Low speed (Y)
989.920 kW Fluid flow 171.69 m³/h Pressure drop 18.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 737.80 not rated not rated not rated not rated not rated
40 1272.26 741.01 not rated not rated not rated not rated
45 1791.06 1270.92 743.70 not rated not rated not rated
50 2304.89 1785.84 1269.85 746.25 not rated not rated
55 2816.26 2296.03 1781.55 1269.22 748.86 not rated
60 3326.27 2803.90 2288.63 1778.53 1269.57 751.87

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 580.24 not rated not rated not rated not rated not rated
40 989.92 582.50 not rated not rated not rated not rated
45 1386.14 988.27 584.43 not rated not rated not rated
50 1777.83 1381.30 987.00 586.30 not rated not rated
55 2167.42 1770.02 1377.33 986.33 588.37 not rated
60 2555.82 2156.74 1763.55 1374.56 986.61 590.90

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 1272.257 220.78 29.1
Low speed (Y) 989.920 171.69 18.6

Dimensions

Dimension drawing of BE-2X980AC1-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 11250 mm
F 2230 mm
G 11850 mm
E1 1250 mm
E2 2400 mm
E3 3600 mm
H 11500 mm
D IN 6"
D OUT 6"
Overall [mm]
Length 11850 mm
Width 2300 mm
Height 2460 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.