BE-2x891AB1-B04T C
1263.69 kW
Defrost: None
Product code: BE-2x880ED5-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 316,183 m³/h |
|---|---|
| External surface | 5,388.8 m² |
| Inner volume | 1,209.7 dm³ |
| Fin material | Aluminium |
| Net weight | 5,465 kg |
| Quantity | 16 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 28,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 60.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-2x880ED5-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 758.14 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1263.17 | 758.31 | not rated | not rated | not rated | not rated |
| 45 | 1753.43 | 1258.91 | 758.35 | not rated | not rated | not rated |
| 50 | 2238.70 | 1745.23 | 1255.36 | 758.80 | not rated | not rated |
| 55 | 2721.66 | 2226.76 | 1738.37 | 1252.87 | 759.83 | not rated |
| 60 | 3203.32 | 2706.06 | 2216.74 | 1733.28 | 1251.86 | 761.71 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 582.10 | not rated | not rated | not rated | not rated | not rated |
| 40 | 959.59 | 582.00 | not rated | not rated | not rated | not rated |
| 45 | 1325.02 | 955.92 | 581.96 | not rated | not rated | not rated |
| 50 | 1686.41 | 1318.21 | 952.86 | 582.18 | not rated | not rated |
| 55 | 2045.93 | 1676.67 | 1312.55 | 950.72 | 582.90 | not rated |
| 60 | 2404.43 | 2033.35 | 1668.56 | 1308.40 | 949.82 | 584.36 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 1263.168 | 219.08 | 35.8 |
| Low speed (Y) | 959.593 | 166.40 | 21.7 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 10050 mm |
| F | 2330 mm |
| G | 10650 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| H | 10300 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 10650 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.