Skip to Content

Dry cooler BE-2x880AD5-B01T C

Dry cooler BE-2x880AD5-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x880AD5-B01T C

Heat rejection i
1257.87 kW
Air flow
326,278 m³/h
Fans
16 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 326,278 m³/h
External surface 5,667.0 m²
Inner volume 823.3 dm³
Fin materialAluminium
Net weight 5,257 kg
Fans
Quantity 16
Diameter 800 mm
Speed 900 rpm
Power 28,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 60.0 dB(A)
Sound power 93.0 dB(A)
Energy class D
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x880AD5-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
1257.872 kW Fluid flow 218.15 m³/h Pressure drop 85.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
969.861 kW Fluid flow 168.20 m³/h Pressure drop 53.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 756.67 not rated not rated not rated not rated not rated
40 1257.87 755.95 not rated not rated not rated not rated
45 1746.06 1252.94 755.31 not rated not rated not rated
50 2229.83 1737.32 1248.78 754.96 not rated not rated
55 2711.58 2217.42 1729.87 1245.60 755.03 not rated
60 3192.20 2695.55 2206.81 1724.08 1243.78 756.07

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 589.41 not rated not rated not rated not rated not rated
40 969.86 588.64 not rated not rated not rated not rated
45 1339.41 965.71 588.01 not rated not rated not rated
50 1705.36 1332.25 962.23 587.67 not rated not rated
55 2069.65 1695.31 1326.23 959.67 587.90 not rated
60 2433.03 2056.78 1686.85 1321.66 958.34 588.84

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 1257.872 218.15 85.2
Low speed (Y) 969.861 168.20 53.6

Dimensions

Dimension drawing of BE-2x880AD5-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 10050 mm
F 2330 mm
G 10650 mm
E1 1250 mm
E2 2400 mm
H 10300 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 10650 mm
Width 2400 mm
Height 2750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.