BE-2x891EB5-B04T C
1256.37 kW
Defrost: None
Product code: BE-2x880AD5-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 326,278 m³/h |
|---|---|
| External surface | 5,667.0 m² |
| Inner volume | 823.3 dm³ |
| Fin material | Aluminium |
| Net weight | 5,257 kg |
| Quantity | 16 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 28,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 60.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-2x880AD5-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 756.67 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1257.87 | 755.95 | not rated | not rated | not rated | not rated |
| 45 | 1746.06 | 1252.94 | 755.31 | not rated | not rated | not rated |
| 50 | 2229.83 | 1737.32 | 1248.78 | 754.96 | not rated | not rated |
| 55 | 2711.58 | 2217.42 | 1729.87 | 1245.60 | 755.03 | not rated |
| 60 | 3192.20 | 2695.55 | 2206.81 | 1724.08 | 1243.78 | 756.07 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 589.41 | not rated | not rated | not rated | not rated | not rated |
| 40 | 969.86 | 588.64 | not rated | not rated | not rated | not rated |
| 45 | 1339.41 | 965.71 | 588.01 | not rated | not rated | not rated |
| 50 | 1705.36 | 1332.25 | 962.23 | 587.67 | not rated | not rated |
| 55 | 2069.65 | 1695.31 | 1326.23 | 959.67 | 587.90 | not rated |
| 60 | 2433.03 | 2056.78 | 1686.85 | 1321.66 | 958.34 | 588.84 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 1257.872 | 218.15 | 85.2 |
| Low speed (Y) | 969.861 | 168.20 | 53.6 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 10050 mm |
| F | 2330 mm |
| G | 10650 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| H | 10300 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 10650 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.