BE-2x980EC5-B01C C
1255.29 kW
Defrost: None
Product code: BE-2x880EC1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 321,694 m³/h |
|---|---|
| External surface | 5,089.2 m² |
| Inner volume | 996.3 dm³ |
| Fin material | Aluminium |
| Net weight | 5,200 kg |
| Quantity | 16 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 28,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 60.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-2x880EC1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 748.65 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1252.96 | 748.96 | not rated | not rated | not rated | not rated |
| 45 | 1743.16 | 1248.99 | 749.15 | not rated | not rated | not rated |
| 50 | 2228.51 | 1735.28 | 1245.47 | 749.48 | not rated | not rated |
| 55 | 2711.62 | 2216.93 | 1728.43 | 1242.80 | 750.14 | not rated |
| 60 | 3193.48 | 2696.43 | 2206.89 | 1723.05 | 1241.47 | 751.79 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 578.47 | not rated | not rated | not rated | not rated | not rated |
| 40 | 958.16 | 578.41 | not rated | not rated | not rated | not rated |
| 45 | 1326.02 | 954.57 | 578.41 | not rated | not rated | not rated |
| 50 | 1689.94 | 1319.35 | 951.60 | 578.66 | not rated | not rated |
| 55 | 2052.03 | 1680.35 | 1313.79 | 949.54 | 579.35 | not rated |
| 60 | 2413.12 | 2039.60 | 1672.33 | 1309.67 | 948.62 | 580.73 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 1252.957 | 217.28 | 47.6 |
| Low speed (Y) | 958.156 | 166.16 | 29.4 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 10050 mm |
| F | 2330 mm |
| G | 10650 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| H | 10300 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 10650 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.