Heat rejection i
1252.96 kW
Air flow
321,694 m³/h
Fans
16 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 321,694 m³/h
External surface 5,089.2 m²
Inner volume 996.3 dm³
Fin materialAluminium
Net weight 5,200 kg
Fans
Quantity 16
Diameter 800 mm
Speed 900 rpm
Power 28,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 60.0 dB(A)
Sound power 93.0 dB(A)
Energy class D
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x880EC1-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
1252.957 kW Fluid flow 217.28 m³/h Pressure drop 47.6 kPa
Heat rejection · Low speed (Y)
958.156 kW Fluid flow 166.16 m³/h Pressure drop 29.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 748.65 not rated not rated not rated not rated not rated
40 1252.96 748.96 not rated not rated not rated not rated
45 1743.16 1248.99 749.15 not rated not rated not rated
50 2228.51 1735.28 1245.47 749.48 not rated not rated
55 2711.62 2216.93 1728.43 1242.80 750.14 not rated
60 3193.48 2696.43 2206.89 1723.05 1241.47 751.79

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 578.47 not rated not rated not rated not rated not rated
40 958.16 578.41 not rated not rated not rated not rated
45 1326.02 954.57 578.41 not rated not rated not rated
50 1689.94 1319.35 951.60 578.66 not rated not rated
55 2052.03 1680.35 1313.79 949.54 579.35 not rated
60 2413.12 2039.60 1672.33 1309.67 948.62 580.73

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 1252.957 217.28 47.6
Low speed (Y) 958.156 166.16 29.4

Dimensions

Dimension drawing of BE-2x880EC1-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 10050 mm
F 2330 mm
G 10650 mm
E1 1250 mm
E2 2400 mm
H 10300 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 10650 mm
Width 2400 mm
Height 2750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.