Dry cooler BE-2x891EB1-C04C C

Dry cooler BE-2x891EB1-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x891EB1-C04C C

Heat rejection i
1247.35 kW
Air flow
412,261 m³/h
Fans
16 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BE — BE = V-type dry cooler.
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 8 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 91 — Ø910 mm
  • G
    Coil tube rows (2nd dimensional letter): B — 3 tube rows
  • H
    Fin spacing: 1 — 2.1 mm
  • I
    Generation code: C — generation C
  • J
    Fan data (fan motor code): 04 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)
  • K
    Delivery version (optional): C — C: container delivery version

Data

Coil
Air flow 412,261 m³/h
External surface 3,146.7 m²
Inner volume 647.2 dm³
Fin materialAluminium
Net weight 4,343 kg
Fans
Quantity 16
Diameter 910 mm
Speed 840 rpm
Power 44,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 71.0 dB(A)
Sound power 103.6 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x891EB1-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
1247.345 kW Fluid flow 216.47 m³/h Pressure drop 98.0 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
987.129 kW Fluid flow 171.31 m³/h Pressure drop 64.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 725.18 not rated not rated not rated not rated not rated
40 1247.35 727.36 not rated not rated not rated not rated
45 1758.39 1246.63 729.26 not rated not rated not rated
50 2265.82 1755.05 1246.25 731.17 not rated not rated
55 2771.50 2259.93 1752.48 1246.34 733.29 not rated
60 3276.29 2763.20 2255.19 1750.89 1247.28 735.85

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 579.07 not rated not rated not rated not rated not rated
40 987.13 580.75 not rated not rated not rated not rated
45 1385.58 986.49 582.26 not rated not rated not rated
50 1780.81 1382.80 986.13 583.85 not rated not rated
55 2174.55 1776.04 1380.77 986.32 585.69 not rated
60 2567.34 2167.71 1772.23 1379.71 987.37 588.04

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 1247.345 216.47 98.0
Low speed (Y) 987.129 171.31 64.7

Dimensions

Dimension drawing of BE-2x891EB1-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 10050 mm
F 2230 mm
G 10650 mm
E1 1250 mm
E2 2400 mm
H 10300 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 10050 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.