Skip to Content

Dry cooler BE-2x880AD1-B01C C

Dry cooler BE-2x880AD1-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x880AD1-B01C C

Heat rejection i
1242.95 kW
Air flow
309,210 m³/h
Fans
16 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 309,210 m³/h
External surface 5,761.7 m²
Inner volume 709.0 dm³
Fin materialAluminium
Net weight 4,829 kg
Fans
Quantity 16
Diameter 800 mm
Speed 900 rpm
Power 28,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 60.0 dB(A)
Sound power 93.0 dB(A)
Energy class D
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x880AD1-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
1242.948 kW Fluid flow 215.57 m³/h Pressure drop 106.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
945.481 kW Fluid flow 163.95 m³/h Pressure drop 65.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 751.84 not rated not rated not rated not rated not rated
40 1242.95 751.02 not rated not rated not rated not rated
45 1720.70 1238.36 750.57 not rated not rated not rated
50 2193.95 1712.50 1234.58 750.56 not rated not rated
55 2665.10 2182.28 1705.69 1231.91 751.11 not rated
60 3135.09 2650.02 2172.54 1700.67 1230.72 752.63

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 578.39 not rated not rated not rated not rated not rated
40 945.48 577.61 not rated not rated not rated not rated
45 1301.66 941.47 576.98 not rated not rated not rated
50 1654.23 1294.74 938.15 576.73 not rated not rated
55 2005.14 1644.56 1289.02 935.81 577.06 not rated
60 2355.14 1992.78 1636.54 1284.84 934.75 578.23

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 1242.948 215.57 106.2
Low speed (Y) 945.481 163.95 65.3

Dimensions

Dimension drawing of BE-2x880AD1-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 10050 mm
F 2230 mm
G 10650 mm
E1 1250 mm
E2 2400 mm
H 10300 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 10650 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.