Skip to Content

Dry cooler BE-2x180CB1-B01C C

Dry cooler BE-2x180CB1-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x180CB1-B01C C

Heat rejection i
165.54 kW
Air flow
44,639 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BE — BE = V-type dry cooler.
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 1 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 80 — Ø800 mm
  • G
    Coil tube rows (2nd dimensional letter): B — 3 tube rows
  • H
    Fin spacing: 1 — 2.1 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 01 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)
  • K
    Delivery version (optional): C — C: container delivery version

Data

Coil
Air flow 44,639 m³/h
External surface 864.2 m²
Inner volume 108.4 dm³
Fin materialAluminium
Net weight 981 kg
Fans
Quantity 2
Diameter 800 mm
Speed 900 rpm
Power 3,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 51.0 dB(A)
Sound power 83.0 dB(A)
Energy class D
Connections
Inlet 2"
Outlet 2"
Defrost
BE-2x180CB1-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
165.544 kW Fluid flow 28.71 m³/h Pressure drop 94.1 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
130.202 kW Fluid flow 22.58 m³/h Pressure drop 61.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 99.16 not rated not rated not rated not rated not rated
40 165.54 98.99 not rated not rated not rated not rated
45 230.28 164.77 98.82 not rated not rated not rated
50 294.46 228.94 164.08 98.69 not rated not rated
55 358.38 292.58 227.77 163.51 98.61 not rated
60 422.16 355.98 290.93 226.80 163.11 98.65

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 78.70 not rated not rated not rated not rated not rated
40 130.20 78.50 not rated not rated not rated not rated
45 180.33 129.50 78.30 not rated not rated not rated
50 229.99 179.16 128.88 78.16 not rated not rated
55 279.43 228.37 178.13 128.36 78.08 not rated
60 328.76 277.37 226.94 177.27 128.00 78.08

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 165.544 28.71 94.1
Low speed (Y) 130.202 22.58 61.5

Dimensions

Dimension drawing of BE-2x180CB1-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 2850 mm
F 2230 mm
G 3450 mm
E1 2450 mm
H 3100 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 3450 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.