BE-291BC1-B04 C
182.72 kW
Defrost: None
Product code: BE-2x180CC1-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 44,136 m³/h |
|---|---|
| External surface | 1,152.3 m² |
| Inner volume | 137.5 dm³ |
| Fin material | Aluminium |
| Net weight | 1,067 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-2x180CC1-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 111.37 | not rated | not rated | not rated | not rated | not rated |
| 40 | 182.99 | 111.03 | not rated | not rated | not rated | not rated |
| 45 | 252.55 | 181.88 | 110.71 | not rated | not rated | not rated |
| 50 | 321.44 | 250.75 | 180.90 | 110.46 | not rated | not rated |
| 55 | 390.02 | 318.97 | 249.17 | 180.11 | 110.30 | not rated |
| 60 | 458.42 | 386.89 | 316.81 | 247.87 | 179.53 | 110.28 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 86.78 | not rated | not rated | not rated | not rated | not rated |
| 40 | 141.16 | 86.45 | not rated | not rated | not rated | not rated |
| 45 | 193.89 | 140.22 | 86.16 | not rated | not rated | not rated |
| 50 | 246.08 | 192.38 | 139.38 | 85.92 | not rated | not rated |
| 55 | 298.02 | 244.04 | 191.07 | 138.70 | 85.77 | not rated |
| 60 | 349.82 | 295.45 | 242.25 | 189.98 | 138.21 | 85.74 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 182.985 | 31.73 | 71.6 |
| Low speed (Y) | 141.163 | 24.48 | 45.1 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 2850 mm |
| F | 2230 mm |
| G | 3450 mm |
| E1 | 2450 mm |
| H | 3100 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3450 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.