BE-2x180DB1-B01T C
147.08 kW
Defrost: None
Product code: BE-2x180DC5-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 43,402 m³/h |
|---|---|
| External surface | 553.8 m² |
| Inner volume | 82.3 dm³ |
| Fin material | Aluminium |
| Net weight | 854 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-2x180DC5-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 86.62 | not rated | not rated | not rated | not rated | not rated |
| 40 | 147.25 | 86.73 | not rated | not rated | not rated | not rated |
| 45 | 206.28 | 146.83 | 86.80 | not rated | not rated | not rated |
| 50 | 264.81 | 205.42 | 146.47 | 86.88 | not rated | not rated |
| 55 | 323.08 | 263.50 | 204.66 | 146.18 | 86.99 | not rated |
| 60 | 381.25 | 321.38 | 262.37 | 204.03 | 146.01 | 87.15 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 68.63 | not rated | not rated | not rated | not rated | not rated |
| 40 | 115.86 | 68.70 | not rated | not rated | not rated | not rated |
| 45 | 161.69 | 115.47 | 68.75 | not rated | not rated | not rated |
| 50 | 207.09 | 160.93 | 115.13 | 68.79 | not rated | not rated |
| 55 | 252.29 | 205.97 | 160.26 | 114.86 | 68.87 | not rated |
| 60 | 297.38 | 250.82 | 204.99 | 159.73 | 114.70 | 69.00 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 147.250 | 25.56 | 46.6 |
| Low speed (Y) | 115.857 | 20.11 | 30.4 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 2250 mm |
| F | 2230 mm |
| G | 2850 mm |
| E1 | 1850 mm |
| H | 2500 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2850 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.