BE-280CD5-B01 C
197.91 kW
Defrost: None
Product code: BE-2x191CB5-B04T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 59,970 m³/h |
|---|---|
| External surface | 850.1 m² |
| Inner volume | 125.9 dm³ |
| Fin material | Aluminium |
| Net weight | 1,082 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-2x191CB5-B04T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 117.18 | not rated | not rated | not rated | not rated | not rated |
| 40 | 197.89 | 117.10 | not rated | not rated | not rated | not rated |
| 45 | 276.78 | 197.20 | 117.02 | not rated | not rated | not rated |
| 50 | 355.07 | 275.51 | 196.58 | 116.96 | not rated | not rated |
| 55 | 433.09 | 353.24 | 274.38 | 196.07 | 116.96 | not rated |
| 60 | 510.96 | 430.71 | 351.63 | 273.46 | 195.73 | 117.05 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 95.24 | not rated | not rated | not rated | not rated | not rated |
| 40 | 159.61 | 95.11 | not rated | not rated | not rated | not rated |
| 45 | 222.40 | 158.94 | 94.99 | not rated | not rated | not rated |
| 50 | 284.69 | 221.22 | 158.34 | 94.90 | not rated | not rated |
| 55 | 346.75 | 283.03 | 220.18 | 157.84 | 94.86 | not rated |
| 60 | 408.67 | 344.60 | 281.55 | 219.33 | 157.49 | 94.91 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 197.885 | 34.34 | 101.8 |
| Low speed (Y) | 159.612 | 27.70 | 69.5 |
| A | 2880 mm |
|---|---|
| B | 2400 mm |
| C | 2850 mm |
| F | 2330 mm |
| G | 3450 mm |
| E1 | 2450 mm |
| H | 3100 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3450 mm |
|---|---|
| Width | 2400 mm |
| Height | 2880 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.