BE-380BD1-B01 C
238.75 kW
Defrost: None
Product code: BE-2x191CC1-B04T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 58,998 m³/h |
|---|---|
| External surface | 1,340.6 m² |
| Inner volume | 177.0 dm³ |
| Fin material | Aluminium |
| Net weight | 1,207 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-2x191CC1-B04T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 144.51 | not rated | not rated | not rated | not rated | not rated |
| 40 | 238.44 | 144.08 | not rated | not rated | not rated | not rated |
| 45 | 329.80 | 237.10 | 143.73 | not rated | not rated | not rated |
| 50 | 420.30 | 327.60 | 235.93 | 143.46 | not rated | not rated |
| 55 | 510.40 | 417.26 | 325.66 | 234.96 | 143.29 | not rated |
| 60 | 600.28 | 506.53 | 414.59 | 324.07 | 234.29 | 143.30 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 114.38 | not rated | not rated | not rated | not rated | not rated |
| 40 | 186.98 | 114.01 | not rated | not rated | not rated | not rated |
| 45 | 257.44 | 185.81 | 113.66 | not rated | not rated | not rated |
| 50 | 327.19 | 255.55 | 184.79 | 113.38 | not rated | not rated |
| 55 | 396.61 | 324.61 | 253.90 | 183.94 | 113.22 | not rated |
| 60 | 465.86 | 393.36 | 322.36 | 252.54 | 183.34 | 113.20 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 238.436 | 41.35 | 80.4 |
| Low speed (Y) | 186.981 | 32.42 | 52.3 |
| A | 2880 mm |
|---|---|
| B | 2400 mm |
| C | 2850 mm |
| F | 2330 mm |
| G | 3450 mm |
| E1 | 2450 mm |
| H | 3100 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3450 mm |
|---|---|
| Width | 2400 mm |
| Height | 2880 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.